Features & Benefits:
1. High Dielectric Strength: Ensures stable insulation and prevents electrical breakdown.
2. Outstanding Oil Absorption: Enables deep oil impregnation, enhancing electrical performance and longevity.
3. Superior Mechanical Strength: Withstands mechanical stress, ensuring durability in demanding applications.
4. High Thermal Stability: Maintains structural integrity under prolonged high temperatures.
6. Low Shrinkage and Dimensional Stability: Minimizes deformation for a precise fit in transformer structures.
7. Versatile Applications: Ideal for oil-filled power transformers, distribution transformers, electric machines, capacitors, and switchgear.
8. Size Options: Available in 1150×800mm, 1000×2000mm, or customized dimensions.
9. Easy Processing: Can be punched, folded, cut, and formed without difficulty.
Basic Specifications:
Properties |
Units |
Values |
≤
1.6mm |
1.6-3.0mm |
>3.0-6.0mm |
Thickness Tolerance |
% |
≤±7.5 |
≤±5.0 |
Density |
g/cm³ |
1.0-1.2 |
Tensile
Strength |
MD |
Mpa |
≥80 |
≥80 |
≥80 |
TD |
≥55 |
≥55 |
≥50 |
Elongation |
MD |
% |
≥6.0 |
TD |
≥8.0 |
Shrinkage |
MD |
% |
<0.7 |
TD |
<1.0 |
Moisture Content |
% |
≤8.0 |
Ash Content |
% |
≤1.0 |
Electric Conductivity |
Ms/m |
≤8.0 |
PH of Water Extractives |
|
6.0-9.0 |
Eectric breakdown Strengthinoil |
KV/m
m |
≥40 |
≥30 |
≥25 |
Application:
* Oil-immersed Transformers: Essential for insulation, improving electrical performance and support.
* Capacitors: Insulating layer between electrodes for stable high-voltage insulation.
* Electric Machines & Appliance: Provides insulation for windings and cores to prevent current leakage.
* Switchgear & Instruments: Isolates circuit components in switches and instruments.
* Current Transformers & Reactors: Provides insulation and support.
* Other Electrical Equipment: Used as a spacer in transformer oil tanks and for making insulation components like slot wedges and winding supports.